How to program the external control for the boiler?
After making the electrical connections, configure the cascade system by accessing the MASTER boiler's control panel and then the TECHNICAL MENU. Select '6. CASCADE' and press ok. In the technical menu, various parameters and information regarding the cascade can be found, such as module delay, minimum modulation power, single burner power, number of sanitary boilers, PI loop time, and cascade settings. Autoconfiguration of the cascade system can be activated via the Autodetect cascade option. Adjust the parameter [6.1.2. Minimum modulation power]. The parameter [6.1.3. Single burner power] must equal the power value of the most powerful generator in the cascade.