How to lock out/tag out ComPact NSX circuit breakers for intervention?

To lock out ComPact NSX circuit breakers, first place the breaker in the "O (OFF)" position to isolate the device. Then, lock it. For toggle-operated breakers, use a locking accessory (up to 3 padlocks). For rotary handles, use a padlock (standard) or key lock (optional). For electrical controls, set the selector to "Manu", open the device, then use the padlocking device or key lock. Always verify that power is cut using a voltage detection device (VAT) before any intervention and wear appropriate personal protective equipment (PPE).

C X

James C.

How to perform the lockout-tagout procedure for ComPact NSX circuit breakers?

To isolate the device, place the circuit breaker in the O (OFF) position. Lock it using the appropriate accessory for your control type: a toggle locking accessory, a rotary handle padlock, or by setting the electric control to Manu and using a lock. Before proceeding, verify the absence of voltage with a detector and ensure the use of appropriate personal protective equipment.

C X

James C.

How to safely lock out (consign) ComPact NSX circuit breakers?

To safely lock out (consign) ComPact NSX circuit breakers, first place the circuit breaker in the O (OFF) position for isolation. The device can only be locked in the O (OFF) position. Locking methods vary: for toggle circuit breakers, use a locking accessory (up to 3 padlocks); for rotary controls, use a padlock or key lock; for electrical controls, set the selector to "Manu," open the device, then use a padlock device or key lock. Always use a voltage detector (VAT) to confirm power is cut before intervention and wear appropriate personal protective equipment (PPE).

C X

James C.

How to safely lockout/tagout ComPact NSX circuit breakers?

To safely lockout/tagout ComPact NSX circuit breakers:

  1. Open and Isolate: Place the circuit breaker in the O (OFF) position. This position is sufficient to isolate the device according to IEC/EN 60947-1 and 2 standards.
  2. Lockout: The device can only be locked in the O (OFF) position. Methods vary by control type:
    • Toggle circuit breaker: Use a locking accessory (removable or integrated) to accommodate up to 3 padlocks (5 to 8 mm diameter).
    • Rotary handle: Lockout is achieved with a padlock (standard in O position) or a key lock (optional).
    • Motor mechanism: Set the selector to Manu, open the device, then use the padlock device or key lock.
  3. Verification: Before any work, always use a voltage detector (VAT) to confirm that the power is truly cut.
  4. Protective Equipment: Wear appropriate personal protective equipment (PPE).