H Y

Jennifer H.

How to adjust frequency settings and monitor parameters before a motor overload (OLF) fault?

Adjust settings via the [REFERENCE SPEED] (rEF-) menu or [Macro configuration] (CFG). To monitor for overload, check the motor thermal state (tHr), which triggers an 'OLF' fault at 118%. Real-time status and fault history can be viewed in the [MONITORING] (MOn-) and [FAULT HISTORY] (pFH-) menus.

A S

Robert A.

How to diagnose the CANopen network and display drive status information?

To diagnose the CANopen network, the [IMAGE CANopen] (CnM-) menu allows displaying drive status information via the following parameters: [Slave NMT status] (nMtS), which shows the NMT status of the CANopen slave (Boot, Stopped, Operational, Pre-Op), and [Error code] (ErCO), which shows the CANopen error register (from 1 to 5).