gefran PROFINET Manuel utilisateur

Ajouter à Mes manuels
38 Des pages
gefran PROFINET Manuel utilisateur | Fixfr
GFXtermo4-GFX4 PROFINET
MANUEL UTILISATEUR
code: 80419B - 06-2014 - FRANCAIS
SOMMAIRE
Introduction..............................................................................................................................................2
Principales Caractéristiques............................................................................................................2
Raccordement des dispositifs...........................................................................................................4
CONNEXIONS ADMISSIBLES.....................................................................................................................4
Schéma de connexion 1 ( 4 zones ) ......................................................................................................4
Schéma de connexion 2 ( 8 zones ) ......................................................................................................4
Schéma de connexion 3 ( 12 zones ) ....................................................................................................5
Schéma de connexion 4 ( 16 zones ) ....................................................................................................6
Description de l’échange de données.........................................................................................7
Du fichier descriptif GSDML à l’échange de données............................................................ 7
Configuration pour le Schéma de Connexion 1 ( 4 zones ) ................................................ 11
Configuration pour le Schéma de Connexion 2 ( 8 zones ) ............................................... 14
Configuration pour le Schéma de Connexion 3 ( 12 zones ) .............................................. 14
Configuration pour le Schéma de Connexion 4 ( 16 zones ) .............................................. 15
SLOT virtuel 5 modbus ......................................................................................................................16
Diagnostic.................................................................................................................................................20
Mauvais réglage du commutateur 7............................................................................................20
Erreur de communication sur le port série modbus.......................................................... 21
BIBLIOTHEQUE SW “Gefran S7” POUr GFX4-GFXtermo4.............................................................. 22
INSTALLATION...........................................................................................................................................22
FONCTIONS...............................................................................................................................................26
80419B_MSW_PROFINET per GFXtermo4-GFX4_06-2014_FRA
1
Introduction
La carte RTE (Real Time Ethernet) est un dispositif qui permet aux esclaves connectés de transmettre et
recevoir des informations à partir du protocole Profinet.
Le schéma conceptuel de raccordement est illustré dans la figure suivante.
il y a :
• Un maître Profinet-controller branché sur un dispositif Profinet-Io (Gefran RTE Profinet Bridge) via le protocole
Profinet (en vert)
• Un maître Modbus RTU en exécution sur la carte RTE ( Gefran Profinet Bridge), branché en série sur un Modbus esclave RTU
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
Principales Caractéristiques
Module Profinet-Io ↔ Modbus RTU
Deux ports Ethernet RJ45 : Eth 0 et Eth 1
Module switch interne
Débit en bauds 100Mbits
Auto_Negotiation, Auto_Polarity, Auto_Crossover
Installation interne
Data transport layer Ethernet II , IEEE 802.3
Support RTC – Real time Cyclic Protocol- Class 1 et Class 2 (non synchronisé)
Support RTA – Real time Acyclic Protocol
Adressage du dispositif via le protocole DCP – Discovery and Configuration Protocol (non DHCP)
Support CL-RPC – Connectionless Remote Procedure Call
Support LLDP – Link Layer Discovery Protocol
Pas de démarrage rapide
32 mots d’entrée (16 bits par mot) pour chaque GFXtermo4-GFX4
32 mots de sortie (16 bits par mot) pour chaque GFXtermo4-GFX4
Intervalle minimum du dispositif pour les données cycliques Profinet cyclic 8ms
Supporte le mode d’adressage GFX4 standard (commutateur 7 sur Off)
commutateurs pour la configuration des fonctions
• Temps minimum de communication série 50 ms pour 16 mots contigus, en utilisant la fonctionnalité custom
map du GFXtermo4-GFX4
2
80419B_MSW_PROFINET per GFXtermo4-GFX4_06-2014_FRA
• Disponibilité de la diode signal DCP sur la façade de l’instrument
80419B_MSW_PROFINET per GFXtermo4-GFX4_06-2014_FRA
3
Raccordement des dispositifs
L’échange interne de données du dispositif GFXtermo4-GFX4 s’effectue au travers de l’encapsulage des
données modbus à l’intérieur des paquets Profinet.
Le port série des dispositifs raccordés doit être configuré :
•
•
•
•
•
Vitesse de connexion sur port série 19200 bauds
Pas de parité
8 bits de données
Les adresses Modbus des noeuds DOIVENT être comprises entre 1 et 4 en séquence. L’instrument GFXtermo4-GFX4 doté de carte Profinet DOIT avoir l’adresse 1
CONNEXIONS ADMISSIBLES
Les possibles combinaisons de connexion et d’adressage des modules GFXtermo4-GFX4 sont illustrées dans
les pages suivantes.
Toute combinaison de connexion qui ne figure pas parmi celles illustrées NE permet PAS la communication Profinet avec un dispositif Controller
Schéma de connexion 1 (4 zones) :
1 GFX4 (ou GFXtermo4) avec adresse de nœud modbus = 1 et commutateur 7 sur Off. Schéma de connexion 2 ( 8 zones ):
2 GFX4 (ou GFXtermo4) avec adresses de nœud modbus = 1 et 2, commutateur 7 sur Off. 4
80419B_MSW_PROFINET per GFXtermo4-GFX4_06-2014_FRA
Schéma de connexion 3 ( 12 zones ) :
3 GFX4 (ou GFXtermo4) avec adresses de nœud modbus = 1,2 et 3 et commutateur 7 sur Off. 80419B_MSW_PROFINET per GFXtermo4-GFX4_06-2014_FRA
5
Schéma de connexion 4 ( 16 zones ) :
4 GFX4 (ou GFXtermo4) avec adresse de nœud modbus = 1,2,3 et 4, commutateur 7 sur Off. 6
80419B_MSW_PROFINET per GFXtermo4-GFX4_06-2014_FRA
Description de l’échange de données
Le module Profinet-Io du dispositif GFXtermo4-GFX4 supporte les typologies de données suivantes
•
•
•
Données de paramétrage (Parameter data)
Données cycliques (Cyclic data)
Données asynchrones (Acyclic data)
La caractérisation de ces données s’effectue via le fichier descriptif du dispositif (fichier GSDML ).
L’interprétation du flux de données doit être connue par l’application qui produit/exploite les informations transmises/reçues par le dispositif. La carte Gefran Profinet-Io fait office de passerelle entre l’univers série modbus et l’univers ethernet Profinet.
Les données suivent ce parcours :
•
•
depuis le maître Profinet-controller vers l’esclave Profinet-Io et inversement, à travers les messageries
acycliques (données asynchrones et paramétrages)
ou bien à travers les données cycliques pour les données de processus rapide.
A l’aide d’un outil de configuration, il est possible de définir les données du dispositif esclave qui seront
échangées à travers les données cycliques rapides.
Du fichier descriptif GSDML à l’échange de données
Pour pouvoir activer l’échange de données, il faut disposer du fichier GSDML descriptif du produit ((GSDMLV2.3-GEFRAN-GFX4-GFXTERMO4-20121119.xml), à télécharger depuis le site www.gefran.com) et l’installer dans
l’environnement de programmation.
Après cette opération, l’on constatera la présence des dossiers Controllers→Geflex avec le module GFXtermo4GFX4 Standard Mode (Fig.1)
Fig 1
Il est alors possible de réaliser la connexion au réseau (2), en déplaçant le dispositif (1), comme illustré dans la
figure 2
Fig 2
80419B_MSW_PROFINET per GFXtermo4-GFX4_06-2014_FRA
7
Au cas où il serait nécessaire de programmer un nom/adresse IP du dispositif, il sera possible d’utiliser les
menus PLC-->Ethernet-->Edit Ethernet Node depuis l’outil de configuration System Manager (Fig.3)
Fig 3
A l’intérieur de la fenêtre Edit Ethernet Node, sélectionner le bouton Browse (Fig. 4) pour rechercher les
nœuds connectés au réseau.
Attendre quelques secondes
Fig 4
8
80419B_MSW_PROFINET per GFXtermo4-GFX4_06-2014_FRA
Au bout de quelques secondes, le système affichera la fenêtre Browse Network, laquelle récapitule les paramètres courants des nœuds connectés au réseau.
Dans l’exemple, le réseau se compose de deux nœuds :
• un contrôleur
• un dispositif gfx4 ou GFXtermo4
Pour modifier les paramètres (Fig. 5) du gfx4 ou GFXtermo4, sélectionner la ligne Device type GEFLEX (1) et valider en appuyant sur la touche OK (2)
Fig 5
80419B_MSW_PROFINET per GFXtermo4-GFX4_06-2014_FRA
9
Dans la fenêtre suivante (Fig. 6), il est possible de programmer le nom/adresse IP du dispositif. Le protocole
DHCP n’est pas supporté
Fig 6
10
80419B_MSW_PROFINET per GFXtermo4-GFX4_06-2014_FRA
Voici comment ajouter un dispositif dans l’outil de configuration, dans la fenêtre Hw-config Configuration pour le Schéma de Connexion 1 ( 4 zones ) :
Fig 7
Dans la figure 7, le dispositif GFXtermo4-GFX4 se trouve dans l’emplacement 1, qui gère 4 zones.
Il existe aussi un canal modbus général dans la fente 5 (voir description du canal modbus).
Si l’on sélectionne l’emplacement 1, comme illustré dans la figure 8:
Fig 8
80419B_MSW_PROFINET per GFXtermo4-GFX4_06-2014_FRA
11
Il est possible de vérifier/modifier le paramétrage des variables Input/Output de processus.
Fig 9
32 variables d’entrée sont disponibles en deux blocs • Input Parameter Record 1 ( 16 mots )
• Input Parameter Record 2 ( 16 mots )
Dans la colonne Value, il est possible de modifier la valeur du paramètre (Fig. 10)
Fig 10
12
80419B_MSW_PROFINET per GFXtermo4-GFX4_06-2014_FRA
32 variables de sortie sont disponibles en deux blocs :
•
•
Output Parameter Record 1
Output Parameter Record 2
Dans ce cas aussi, il est possible d’intervenir dans la colonne Value pour modifier les variables de sortie (Fig.11)
Fig 11
80419B_MSW_PROFINET per GFXtermo4-GFX4_06-2014_FRA
13
Configuration pour le Schéma de Connexion 2 (8 zones ) :
Depuis l’outil de configuration, sélectionner le module GFXtermo4-GFX4 Standard Mode et le déplacer dans l’emplacement 2.
Le module modbus se trouve dans l’emplacement 5 (Fig.12)
Fig 12
Dans la fenêtre des propriétés de chaque module, il est possible de paramétrer les données d’entrée/sortie, comme illustré plus haut.
Configuration pour le Schéma de Connexion 3 (12 zones ) :
Depuis l’outil de configuration, sélectionner le module GFXtermo4-GFX4 Standard Mode et le déplacer dans l’emplacement 2, puis dans l’emplacement 3. La module modbus se trouve dans l’emplacement 5 (Fig.13).
Fig 13
Dans la fenêtre des propriétés de chaque module, il est possible de paramétrer les données d’entrée/sortie, comme illustré plus haut.
14
80419B_MSW_PROFINET per GFXtermo4-GFX4_06-2014_FRA
Configuration pour le Schéma de Connexion 4 ( 16 zones ) :
Depuis l’outil de configuration, sélectionner le module GFXtermo4-GFX4 Standard Mode et le déplacer dans l’emplacement 2 , 3 puis dans l’emplacement 4. La module modbus se trouve dans l’emplacement 5 (Fig.14).
Fig 14
Dans la fenêtre des propriétés de chaque module, il est possible de paramétrer les données d’entrée/sortie, comme illustré plus haut.
80419B_MSW_PROFINET per GFXtermo4-GFX4_06-2014_FRA
15
L’emplacement virtuelle 5 modbus
L’emplacement 5 (Fig.15) est un dispositif virtuel qui permet d’encapsuler une commande modbus parmi les données Profinet cycliques.
Fig 15
Dans les paramètres du module, il est possible de configurer certains aspects liés à la communication.
•
Fault Mode (Fig.16) : en cas de coupure de la communication Profinet, des actions peuvent être entreprises
pour configurer les modules comme suit
√
√
√
√
N’entreprendre aucune action
Commander le dispositif en mode Software Off
Commander le dispositif en mode manuel
Configurer SP2 en tant que Setpoint
Fig 16
•
Modbus Read Mode (Fig.17) :
√
√
Normal Modbus read: tous les 32 mots d’entrée sont ajoutés en lecture (Input parameter record 1 et Input
parameter record 2)
Half Modbus read: si les variables en lecture nécessaires pour l’application sont égales au maximum à
16 mots, seuls les Input parameter record 1 sont actualisés.
Fig 17
16
80419B_MSW_PROFINET per GFXtermo4-GFX4_06-2014_FRA
L’emplacement 5 modbus a des dimensions égales à 8 octets en écriture et 8 octets en lecture. Par le biais de ce
canal, il est possible de lire ou d’écrire n’importe quelle variable parmi celles publiées dans la cartographie modbus
des modules GFXtermo4-GFX4 connectés au réseau.
Canal modbus, emplacement 5 de sortie, 8 octets
Octet 1
Octet 2
Mot déclencheur
d’interrogation
Canal de sortie Modbus
Octet 3
Adresse
Modbus
Octet 4
Octet 5
Octet 6
Octet 7
Octet 8
Code Fonction
Données
1
Données
2
Données
3
Données
4
Canal modbus, emplacement 5 d’entrée, 8 octets
Octet 1
Octet 2
Mot déclencheur
de réponse
OFFSET D’OCTETS
Modbus INput channel
Octet 3
Adresse
Modbus
Octet 4
Octet 5
Octet 6
Octet 7
Octet 8
Code Fonction
Données
1
Données
2
Données
3
Données
4
PARAMETRE
0
Mot déclencheur
d’interrogation/
réponse
2
Adresse ESCLAVE
4
Données 1
3
5
6
7
Description
Code Fonction
Données 2
Données 3
Données 4
80419B_MSW_PROFINET per GFXtermo4-GFX4_06-2014_FRA
Description
Mot DECLENCHEUR d’interrogation : il doit être
augmenté de 1 à chaque nouvelle interrogation.
La réponse est valide lorsque le mot déclencheur de réponse est le même que le mot DECLENCHEUR d’interrogation.
Adresse MODBUS du GFXtermo4-GFX4
Code Fonction Lecture/Ecriture Bit/Mot
Dépend du CODE FONCTION
Dépend du CODE FONCTION
Dépend du CODE FONCTION
Dépend du CODE FONCTION
17
Lecture bit (1,2)
INTERROGATION
TRG
ADRESSE
ESCLAVE
CODE
FONCTION
ADRESSE
BIT OCTET +
SIGNIF.
ADRESSE BIT
OCTET SIGNIF.
Mot
déclencheur
d’interrogation
Adresse
Esclave
1 ou 2
Adresse du
bit à lire
Adresse du
bit à lire
TRG
ADRESSE
ESCLAVE
CODE
FONCTION
Nombre
d’octets
Mot
déclencheur de
réponse
Adresse
Esclave
Code
fonction
de confirmation
NOMBRE DE
BITS
OCTET +
SIGNIF.
NOMBRE DE
BITS
OCTET SIGNIF.
BIT
BIT
#
Valeur des
bits (1÷8)
Valeur des
bits (9÷16)
Fictif
NUMERO
WORD +
SIGNIFICATIVO
NUMERO
WORD SIGNIFICATIVO
MOT DE DONNEES - SIGNIF.
#
REPONSE
Nombre
d’octets
(1 ou 2)
Nombre de
bits à lire.
Doit être = 0
Nombre de
bits à lire.
Lecture d’un mot (3,4)
TRG
ADRESSE
ESCLAVE
CODE
FONCTION
Mot
déclencheur
d’interrogation
Adresse
Esclave
3 ou 4
TRG
Mot
déclencheur de
réponse
ADRESSE
ESCLAVE
Adresse
Esclave
CODE
FONCTION
Code
fonction
INTERROGATION
ADRESSE
BIT OCTET +
SIGNIF.
Adresse mot
à lire
ADRESSE BIT
OCTET SIGNIF.
Adresse mot
à lire
REPONSE
NOMBRE
D’OCTETS
Nombre
d’octets lus
MOT DE DONNEES + SIGNIF.
Valeur
0
1
Valeur
Fictif
BIT
#
Ecriture bit (5)
TRG
Mot
déclencheur
d’interrogation
TRG
Mot
déclencheur de
réponse
18
ADRESSE
ESCLAVE
Adresse
esclave
ADRESSE
ESCLAVE
CODE
FONCTION
5
CODE
FONCTION
Adresse Code de
esclave confirmation
INTERROGATION
ADRESSE +
SIGNIF.
Adresse bit
à écrire
ADRESSE SIGNIF.
Adresse bit à Valeur du bit
écrire
00 = off ou
FFhex = on)
REPONSE
0
ADRESSE +
SIGNIF.
ADRESSE SIGNIF.
BIT
00
Adresse bit
écrite
Adresse bit
écrite
Valeur du bit
00 = off ou
FFhex = on)
0
80419B_MSW_PROFINET per GFXtermo4-GFX4_06-2014_FRA
Ecriture d’un mot (6)
TRG
Mot
déclencheur
d’interrogation
TRG
Mot
déclencheur de
réponse
ADRESSE
ESCLAVE
ADRESSE
ESCLAVE
ADRESSE
ESCLAVE
CODE
FONCTION
6
CODE
FONCTION
Adresse Code de
esclave confirmation
INTERROGATION
ADRESSE +
SIGNIF
ADRESSE SIGNIF
Adresse
mot
à écrire
Adresse
mot
à écrire
REPONSE
ADRESSE +
SIGNIF
ADRESSE SIGNIF
Adresse
mot écrite
Adresse
mot écrite
DONNEES +
SIGNIF.
DONNEES SIGNIF.
Valeur mot
à écrire
Valeur mot
à écrire
DONNEES +
SIGNIF.
DONNEES SIGNIF.
Valeur
mot écrite
Valeur
mot écrite
En cas d’erreur, la valeur Code Fonction d’interrogation, ajoutée à 80hex, est restituée dans le Code Fonction du
message de réponse.
TRG
Mot
déclencheur de
réponse
Code d’Erreur
1
illegal FC
ADRESSE
ESCLAVE
Confirmer
adresse
Esclave
CODE
FONCTION
Code
fonction
d’interrogation
+ 80hex
2
illegal data
address
REPONSE
Code
d’erreur
Code
d’erreur
3
illegal data
80419B_MSW_PROFINET per GFXtermo4-GFX4_06-2014_FRA
#
#
#
fictif
fictif
fictif
9
illegal number
of data
10
Data is read
Only
19
Diagnostic
Mauvais réglage du commutateur 7
Comme cela a déjà été rappelé, le dispositif GFXtermo4-GFX4 DOIT fonctionner en mode Geflex standard, avec
le commutateur 7 sur OFF lors de la mise sous tension.
Si le dispositif démarre avec le commutateur 7 sur ON, la communication ne peut avoir lieu. Un message d’erreur
(Fig.18) est alors envoyé au poste Profinet-Controller.
Fig 18
L’emplacement indiquée dans le message de diagnostic correspond au nœud du dispositif avec le commutateur 7
mal réglé.
20
80419B_MSW_PROFINET per GFXtermo4-GFX4_06-2014_FRA
Défaut de communication sur le Modbus serie
Cela apparaît lorsque la communication entre le Maître Modbus de la carte Profinet-IO et l’escalve Modbus dans
la GFXtermo4-GFX4 échouse, comme illustré sur la figure 19
Figure 19
Quand cela apparaît, le module Profinet-IO envoie au Profinet-Controller le message d’erreur de communicaton
Fig.20
Figure 20
Le slot spécifié sur message d’erreur correspond au noeud de l’appareil sur lequel le défaut apparaît.
80419B_MSW_PROFINET per GFXtermo4-GFX4_06-2014_FRA
21
BIBLIOTHÈQUES SW “Gefran S7” pour GFX4-GFXtermo4
INSTALLATION
GEFRAN S.p.A. fournit une série de fichiers de la bibliothèque pour faciliter l’installation de la GFX4 et GFXtermo4 et
de la gestion des données de processus dans l’environnement de SIEMENS STEP7.
Ces bibliothèques sont contenues dans un fichier compressé “GefranProfinet_V2-00.zip” sur le CD inclus avec le
produit ou téléchargeable sur www.gefran.com
Après le lancement de SIMATIC Manager, cliquez sur désarchivez dans le menu déroulant fichier et ouvrez le fichier
“GefranProfinet_V2-00.zip” dans le dossier dans lequel il a été copié.
Puis selectionner le dossier de destinations dans ..STEP7/S7Proj.
A la fin de l’extraction, en sélectionnant la commande “Ouvrir projet” dans le menu déroulant “Fichier” et on pourra
accéder à la librairie “GefranProfinet_V2-00” du GFX4 et GFXtermo4.
22
80419B_MSW_PROFINET per GFXtermo4-GFX4_06-2014_FRA
Elle contient des Blocs Fonctionnels, des Blocs de Données et des Fonctions:
GFX4 en modalitè HIGH PERFORMANCE
OBJECT
UDT6
DESCRIPTION
Data type for managing Process datA
FC4
Management of Process Data area
FC3
anagement function data PARAMETRIC
UDT5
FB1
FB15
Block acyclic data exchange
Function block to manage parameters
Function block to manage parameter recipes
80419B_MSW_PROFINET per GFXtermo4-GFX4_06-2014_FRA
23
FONCTIONS
UDT6
Type de données pour gestion données de processus des GFX4
Bloc des données en lecture depuis l’adresse word 0 jusqu’à l’adresse word 62
Bloc des données en écriture depuis l’adresse word 64 jusqu’à l’adresse word 126
Address
Name
0.0
+ 0.0 GFX4_Read_W01
+ 2.0 GFX4_Read_W02
+ 4.0 GFX4_Read_W03
+ 6.0 GFX4_Read_W04
+ 8.0 GFX4_Read_W05
+ 10.0 GFX4_Read_W06
+ 12.0 GFX4_Read_W07
+ 14.0 GFX4_Read_W08
+ 16.0 GFX4_Read_W09
+ 18.0 GFX4_Read_W10
+ 20.0 GFX4_Read_W11
+ 22.0 GFX4_Read_W12
+ 24.0 GFX4_Read_W13
+ 26.0 GFX4_Read_W14
+ 28.0 GFX4_Read_W15
+ 30.0 GFX4_Read_W16
+ 32.0 GFX4_Read_W17
+ 34.0 GFX4_Read_W18
+ 36.0 GFX4_Read_W19
+ 38.0 GFX4_Read_W20
+ 40.0 GFX4_Read_W21
+ 42.0 GFX4_Read_W22
+ 44.0 GFX4_Read_W23
+ 46.0 GFX4_Read_W24
+ 48.0 GFX4_Read_W25
+ 50.0 GFX4_Read_W26
+ 52.0 GFX4_Read_W27
+ 54.0 GFX4_Read_W28
+ 56.0 GFX4_Read_W29
+ 58.0 GFX4_Read_W30
+ 60.0 GFX4_Read_W31
+ 62.0 GFX4_Read_W32
+ 64.0 GFX4_Write_W01
+ 66.0 GFX4_Write_W02
+ 68.0 GFX4_Write_W03
+ 70.0 GFX4_Write_W04
24
Type
STRUCT
Initial
value
Comment
INT
0
GFX4 Read Process Word 01
INT
0
GFX4 Read Process Word 02
INT
0
GFX4 Read Process Word 03
INT
0
GFX4 Read Process Word 04
INT
0
GFX4 Read Process Word 05
INT
0
GFX4 Read Process Word 06
INT
0
GFX4 Read Process Word 07
INT
0
GFX4 Read Process Word 08
INT
0
GFX4 Read Process Word 09
INT
0
GFX4 Read Process Word 10
INT
0
GFX4 Read Process Word 11
INT
0
GFX4 Read Process Word 12
INT
0
GFX4 Read Process Word 13
INT
0
GFX4 Read Process Word 14
INT
0
GFX4 Read Process Word 15
INT
0
GFX4 Read Process Word 16
INT
0
GFX4 Read Process Word 17
INT
0
GFX4 Read Process Word 18
INT
0
GFX4 Read Process Word 19
INT
0
GFX4 Read Process Word 20
INT
0
GFX4 Read Process Word 21
INT
0
GFX4 Read Process Word 22
INT
0
GFX4 Read Process Word 23
INT
0
GFX4 Read Process Word 24
INT
0
GFX4 Read Process Word 25
INT
0
GFX4 Read Process Word 26
INT
0
GFX4 Read Process Word 27
INT
0
GFX4 Read Process Word 28
INT
0
GFX4 Read Process Word 29
INT
0
GFX4 Read Process Word 30
INT
0
GFX4 Read Process Word 31
INT
0
GFX4 Read Process Word 32
INT
0
GFX4 Write Process Word 01
INT
0
GFX4 Write Process Word 02
INT
0
GFX4 Write Process Word 03
INT
0
GFX4 Write Process Word 04
80419B_MSW_PROFINET per GFXtermo4-GFX4_06-2014_FRA
Address
Name
+ 72.0 GFX4_Write_W05
+ 74.0 GFX4_Write_W06
+ 76.0 GFX4_Write_W07
+ 78.0 GFX4_Write_W08
+ 80.0 GFX4_Write_W09
+ 82.0 GFX4_Write_W10
+ 84.0 GFX4_Read_W11
+ 86.0 GFX4_Read_W12
+ 88.0 GFX4_Read_W13
+ 90.0 GFX4_Read_W14
+ 92.0 GFX4_Read_W15
+ 94.0 GFX4_Write_W16
+ 96.0 GFX4_Write_W17
+ 98.0 GFX4_Write_W18
+ 100.0 GFX4_Write_W19
+ 102.0 GFX4_Write_W20
+ 104.0 GFX4_Write_W21
+ 106.0 GFX4_Write_W22
+ 108.0 GFX4_Write_W23
Type
INT
Initial
value
Comment
0
GFX4 Write Process Word 05
INT
0
GFX4 Write Process Word 06
INT
0
GFX4 Write Process Word 07
INT
0
GFX4 Write Process Word 08
INT
0
GFX4 Write Process Word 09
INT
0
GFX4 Write Process Word 10
INT
0
GFX4 Write Process Word 11
INT
0
GFX4 Write Process Word 12
INT
0
GFX4 Write Process Word 13
INT
0
GFX4 Write Process Word 14
INT
0
GFX4 Write Process Word 15
INT
0
GFX4 Write Process Word 16
INT
0
GFX4 Write Process Word 17
INT
0
GFX4 Write Process Word 18
INT
0
GFX4 Write Process Word 19
INT
0
GFX4 Write Process Word 20
INT
0
GFX4 Write Process Word 21
INT
0
GFX4 Write Process Word 22
INT
0
GFX4 Write Process Word 23
+ 112.0 GFX4_Write_W25
INT
0
GFX4 Write Process Word 24
INT
0
GFX4 Write Process Word 25
+ 116.0 GFX4_Write_W27
INT
0
GFX4 Write Process Word 26
INT
0
GFX4 Write Process Word 27
INT
0
GFX4 Write Process Word 28
INT
0
GFX4 Write Process Word 29
INT
0
GFX4 Write Process Word 30
INT
0
GFX4 Write Process Word 31
INT
0
GFX4 Write Process Word 32
+ 110.0 GFX4_Write_W24
+ 114.0 GFX4_Write_W26
+ 118.0 GFX4_Write_W28
+ 120.0 GFX4_Write_W29
+ 122.0 GFX4_Write_W30
+ 124.0 GFX4_Write_W31
+ 126.0 GFX4_Write_W32
= 128.0
END_STRUCT
80419B_MSW_PROFINET per GFXtermo4-GFX4_06-2014_FRA
25
FONCTIONS
FC4 “FC_PD_GFX4” (FUNCTION CALL) ”
Fonction de gestion traite la zone GFX4 donné. Cette fonction met à disposition la zone d’échange de données de
processus entre le PLC and GFX4 (ou GFXtermo4) dans le bloc données crée avec l’UDT6 décrit plus haut.
FC4 doit être appelée à chaque scrutation pour assurer la mise à jour des données.
Deux paramètres d’entrée sont requis:
1. FirstByte :
2. DBNr :
(INT) La première adresse mémoire attribuée au rack GFX4 (ou GFXtermo4) dans la configuration
matérielle.
(INT) le numéro du bloc de données crée avec l’UDT6 pour l’échange de données entre la GFX4
(ou GFXtermo4) et le PLC
First byte
26
80419B_MSW_PROFINET per GFXtermo4-GFX4_06-2014_FRA
La figure ci-dessous montre une connexion avec 4 esclaves
80419B_MSW_PROFINET per GFXtermo4-GFX4_06-2014_FRA
27
UDT5
Bloc d’échange acyclique des données
Address
Name
0.0
+ 0.0 Trigger
Type
STRUCT
Initial
value
Comment
+ 1.0 Cont
BYTE
B#16#0
Reserved
BYTE
B#16#0
Reserved
+ 4.0 ParamByte3
WORD
W#16#0
Request Byte 1 e 2
+ 5.0 ParamByte4
BYTE
B#16#0
Request Byte 3
BYTE
B#16#0
Request Byte 4
+ 7.0 ParamByte6
BYTE
B#16#0
Request Byte 5
+ 8.0 ParamByte7
BYTE
B#16#0
Request Byte 6
BYTE
B#16#0
Request Byte 7
+ 10.0 StatusWord1
BYTE
B#16#0
Request Byte 8
+ 12.0 StatusByte3
WORD
W#16#0
Answer Byte 1 e 2
BYTE
B#16#0
Answer Byte 3
+ 14.0 StatusByte5
BYTE
B#16#0
Answer Byte 4
+ 15.0 StatusByte6
BYTE
B#16#0
Answer Byte 5
BYTE
B#16#0
Answer Byte 6
+ 17.0 StatusByte8
BYTE
B#16#0
Answer Byte 7
BYTE
B#16#0
Answer Byte 8
+ 2.0 ParamWord1
+ 6.0 ParamByte5
+ 9.0 ParamByte8
+ 13.0 StatusByte4
+ 16.0 StatusByte7
+ 18.0 ParamWriteDiag
+ 20.0 StatusReadDiag
= 22.0
INT
0
Status Word write param operation
INT
0
Status Word read param operation
END_STRUCT
FC3 “FC_CFG_GFX4” (FUNCTION CALL) ”
Fonction gestion de l’espace des données paramétrique du GFX4
Cette fonction s’occupe de rendre disponibles, dans le bloc de données créé avec les UDT5 décrits au paragraphe
précédent, les Données Paramétriques de l’instrument, nécessaires pour le fonctionnement du FB1.
Le FC doit être rappelé dans l’OB1, sans conditions, de manière à ce que les données soient réactualisées lors de
chaque exploration
Deux paramètres d’entrée seront demandés:
1.
FirstByte : (INT) est la première adresse de mémoire attribuée au GFX4 (ou GFXtermo4) dans la
configuration matérielle.
2.
DBNr : (INT) est le numéro du bloc de données créé avec l’UDT5 pour l’échange de données entre le GFX4
(ou GFXtermo4) et le PLC.
28
80419B_MSW_PROFINET per GFXtermo4-GFX4_06-2014_FRA
First byte
80419B_MSW_PROFINET per GFXtermo4-GFX4_06-2014_FRA
29
BLOCS DE FONCTIONS
Tous les Blocs de Fonctions requièrent un DB d’instance, qui peut être librement attribué. Ils ne sont rappelés qu’à la
demande et maintenus actifs jusqu’au terme de l’opération.
Généralement, l’on définit un bit qui habilite la branche (EN) et qui est remis à zéro avec le front de montée du bit “Opération terminée” (Done).
FB1 “FB_OP_GFX4” (FUNCTION BLOCK)
Il s’occupe de gérer les principales opérations des Données Paramétriques pour la configuration du GFX4.
Quatre opérations sont disponibles :
1. Lecture bit (op. code 1)
2. Lecture mot (op. code 3)
3. Ecriture bit (op. code 5)
4. Ecriture mot (op. code 6)
Ce bloc requiert 5 paramètres d’entrée et répond par 4 paramètres de sortie.
Paramètres d’entrée :
1. DBNr (INT) : numéro du bloc de données associé au GFX4 à interroger ou commander.
2. SlaveNr (INT) : adresse MODBUS de l’esclave avec lequel on souhaite opérer.
3. OPCode (INT) : code opération permettant à la fonction de savoir si l’on veut lire ou écrire un mot ou un bit.
Les codes opérations sont les suivants:
• Lecture bit Code Opération : 1
• Lecture mot Code Opération : 3
• Ecriture bit Code Opération : 5
• Ecriture mot Code Opération : 6
4. Address (INT) : adresse du mot/bit à lire/écrire.
(Se reporter au manuel GFX4 pour l’identification des adresses MODBUS des mots/bits).
5. INValue (INT) : valeur à écrire dans le mot ou le bit sélectionné.
En cas d’écriture d’un bit, seules les valeurs 1 et 0 sont naturellement admises.
Dans les opérations de lecture, ce paramètre est ignoré.
30
80419B_MSW_PROFINET per GFXtermo4-GFX4_06-2014_FRA
Paramètres de sortie :
- Done (BOOL): sa valeur est égale à 1 lorsque l’opération de lecture est terminée.
- OUTValue (INT) : valeur lue dans le mot ou le bit spécifié.
Dans les opérations d’écriture, elle est égale à 1 si l’action a bien abouti ou à 0 si elle s’est terminée par une erreur
- Error (BOOL): sa valeur est égale à 1 lorsque l’opération s’est terminée par une erreur.
- ErrCode (INT): code de l’erreur constatée :
1 Illegal function
2 Illegal data address
3 Illegal data value
6 Slave device busy
9 Illegal number data
10 Read only data
20 Timeout Communication
21 Input value error
80419B_MSW_PROFINET per GFXtermo4-GFX4_06-2014_FRA
31
FB15 “FB_RCP_GFX4” (FUNCTION BLOCK)
Stockage dans un DB d’un jeu de paramètres en provenance d’un GFX4 ou bien envoi vers un GFX4 d’un jeu de
paramètres contenus dans un DB.
Paramètres d’entrée :
- DB_GFX (INT) : indiquer le numéro (paramètre en chiffres ou variable INT qui en contienne la valeur) du DB associé au GFX4 sur lequel on souhaite opérer.
- DBIST (BLOCK_DB) : indiquer le nom (utiliser le nom symbolique du DB ou l’indication “DBxx” en entier) du DB
d’instance du FB1 “OP_GFX4”, destiné au GFX4.
- GFXNr (INT) : l’adresse du GFX4 avec lequel on souhaite opérer.
- RCP_DB (INT) : le numéro du DB dans ou depuis lequel écrire/lire le jeu de données.
- Funct (BOOL) : le type d’opération à exécuter :
False = Store (enregistrer les paramètres du GFX4 dans le DB)
True = Load (télécharger dans le GFX4 les paramètres enregistrés dans le DB)
- ParamNr (INT) : le nombre de paramètres à enregistrer/lire.
- ParamListDB (INT) : numéro du DB dans lequel chaque ligne spécifie l’adresse Modbus des paramètres à lire/écrire.
Paramètres de sortie :
- Done (BOOL) : sa valeur est égale à 1 lorsque l’opération est terminée.
- Error (BOOL) : sa valeur est égale à 1 lorsqu’une erreur est survenue pendant l’opération d’écriture.
- ErrorCode (INT) : en cas d’erreur, son code s’affiche
1 Fonction illicite
2 Adresse données illicite
3 Valeur données illicite
6 Dispositif esclave occupé
9 Nombre de données illicite
10 Données en lecture seulement
20 Timeout communication
21 Erreur valeur d’entrée
- ErrorParamNr (INT) : en cas d’erreur, le numéro ordinaire du DB apparaît, avec la liste des adresses du paramètre
qui a provoqué l’erreur
32
80419B_MSW_PROFINET per GFXtermo4-GFX4_06-2014_FRA
UDT4
Liste des adresses Modbus des paramètres utilisés dans FB15
Address
Name
0.0
+ 0.0 tYP_Zone_1
+ 2.0 HiS_Zone_1
+ 4.0 HStA_Zone_1
+ 6.0 Ctr_Zone_1
+ 8.0 HpH_Zone_1
+ 10.0 HpL_Zone_1
+ 12.0 HiL_Zone_1
+ 14.0 ALn_Zone_1
+ 16.0 A1r_Zone_1
+ 18.0 A2r_Zone_1
+ 20.0 A1t_Zone_1
+ 22.0 A2t_Zone_1
+ 24.0 HbF_Zone_1
+ 26.0 Hbt_Zone_1
+ 28.0 Lbt_Zone_1
+ 30.0 HPb_Zone_1
+ 32.0 CPb_Zone_1
+ 34.0 Hit_Zone_1
+ 36.0 Cit_Zone_1
+ 38.0 Hdt_Zone_1
+ 40.0 Cdt_Zone_1
+ 42.0 AL1_Zone_1
+ 44.0 AL2_Zone_1
+ 46.0 ALHb_Zone_1
+ 48.0 tYP_Zone_2
+ 50.0 HiS_Zone_2
+ 52.0 HStA_Zone_2
+ 54.0 Ctr_Zone_2
+ 56.0 HpH_Zone_2
+ 58.0 HpL_Zone_2
+ 60.0 HiL_Zone_2
+ 62.0 ALn_Zone_2
+ 64.0 A1r_Zone_2
+ 66.0 A2r_Zone_2
+ 68.0 A1t_Zone_2
+ 70.0 A2t_Zone_2
+ 72.0 HbF_Zone_2
+ 74.0 Hbt_Zone_2
+ 76.0 Lbt_Zone_2
+ 78.0 HPb_Zone_2
+ 80.0 CPb_Zone_2
Type
STRUCT
Initial
value
Comment
INT
1424
Probe/Input type (1424) Zone 1
INT
1426
Max Input (1426) Zone 1
INT
1429
Max limit TA (1429) Zone 1
INT
1204
Control Type (1204) Zone 1
INT
1066
Max power heating % (1066) Zone 1
INT
1278
Min power heating % (1278) Zone 1
INT
1050
Max Setpoint (1050) Zone 1
INT
1219
Alarms enabling (1219) Zone 1
INT
1239
Alarm 1 reference (1239) Zone 1
INT
1240
Alarm 2 reference (1240) Zone 1
INT
1430
Alarm 1 type (1430) Zone 1
INT
1431
Alarm 2 type (1431) Zone 1
INT
1081
Alarm HB type (1081) Zone 1
INT
1080
Delay time for alarm HB (1080) Zone 1
INT
1068
Delay time for alarm LBA (1068) Zone 1
INT
1029
Heating Proportional bande (1029) Zone 1
INT
1030
Cooling Proportional bande (1030) Zone 1
INT
1031
Heating Integral Time (1031) Zone 1
INT
1100
Cooling Integral Time (1100) Zone 1
INT
1032
Heating Derivative Time (1032) Zone 1
INT
1101
Cooling Derivative Time (1101) Zone 1
INT
1036
Alarm 1 Min Temp (1036) Zone 1
INT
1037
Alarm 2 Max Temp (1037) Zone 1
INT
1079
Alarm Hb Amper (1079) Zone 1
INT
2448
Probe/Input type (2448) Zone 2
INT
2450
Max Input (2450) Zone 2
INT
2453
Max limit TA (2453) Zone 2
INT
2228
Control Type (2228) Zone 2
INT
2090
Max power heating % (2090) Zone 2
INT
2302
Min power heating % (2302) Zone 2
INT
2074
Max Setpoint (2074) Zone 2
INT
2243
Alarms enabling (2243) Zone 2
INT
2263
Alarm 1 reference (2263) Zone 2
INT
2264
Alarm 2 reference (2264) Zone 2
INT
2454
Alarm 1 type (2454) Zone 2
INT
2455
Alarm 2 type (2455) Zone 2
INT
2105
Alarm HB type (2105) Zone 2
INT
2104
Delay time for alarm HB (2104) Zone 2
INT
2092
Delay time for alarm LBA (2092) Zone 2
INT
2053
Heating Proportional bande (2053) Zone 2
INT
2054
Cooling Proportional bande (2054) Zone 2
80419B_MSW_PROFINET per GFXtermo4-GFX4_06-2014_FRA
33
Address
Name
Initial
value
Comment
+ 82.0 Hit_Zone_2
INT
+ 86.0 Hdt_Zone_2
INT
2124
Cooling Integral Time (2124) Zone 2
+ 88.0 Cdt_Zone_2
INT
2056
Heating Derivative Time (2056) Zone 2
INT
2125
Cooling Derivative Time (2125) Zone 2
+ 92.0 AL2_Zone_2
INT
2060
Alarm 1 Min Temp (2060) Zone 2
+ 94.0 ALHb_Zone_2
INT
2061
Alarm 2 Max Temp (2061) Zone 2
INT
2103
Alarm Hb Amper (2103) Zone 2
+ 98.0 HiS_Zone_3
INT
4496
Probe/Input type (4496) Zone 3
INT
4498
Max Input (4498) Zone 3
+ 102.0 Ctr_Zone_3
INT
4501
Max limit TA (4501) Zone 3
INT
4276
Control Type (4276) Zone 3
+ 106.0 HpL_Zone_3
INT
4138
Max power heating % (4138) Zone 3
+ 108.0 HiL_Zone_3
INT
4350
Min power heating % (4350) Zone 3
INT
4122
Max Setpoint (4122) Zone 3
+ 112.0 A1r_Zone_3
INT
4291
Alarms enabling (4291) Zone 3
+ 114.0 A2r_Zone_3
INT
4311
Alarm 1 reference (4311) Zone 3
INT
4312
Alarm 2 reference (4312) Zone 3
+ 118.0 A2t_Zone_3
INT
4502
Alarm 1 type (4502) Zone 3
+ 120.0 HbF_Zone_3
INT
4503
Alarm 2 type (4503) Zone 3
INT
4153
Alarm HB type (4153) Zone 3
+ 124.0 Lbt_Zone_3
INT
4152
Delay time for alarm HB (4152) Zone 3
+ 126.0 HPb_Zone_3
INT
4140
Delay time for alarm LBA (4140) Zone 3
INT
4101
Heating Proportional bande (4101) Zone 3
+ 130.0 Hit_Zone_3
INT
4102
Cooling Proportional bande (4102) Zone 3
INT
4103
Heating Integral Time (4103) Zone 3
+ 134.0 Hdt_Zone_3
INT
4172
Cooling Integral Time (4172) Zone 3
INT
4104
Heating Derivative Time (4104) Zone 3
+ 138.0 AL1_Zone_3
INT
4173
Cooling Derivative Time (4173) Zone 3
+ 140.0 AL2_Zone_3
INT
4108
Alarm 1 Min Temp (4108) Zone 3
INT
4109
Alarm 2 Max Temp (4109) Zone 3
+ 144.0 tYP_Zone_4
INT
4151
Alarm Hb Amper (4151) Zone 3
+ 146.0 HiS_Zone_4
INT
8592
Probe/Input type (8592) Zone 4
INT
8594
Max Input (8594) Zone 4
+ 150.0 Ctr_Zone_4
INT
8597
Max limit TA (8597) Zone 4
+ 152.0 HpH_Zone_4
INT
8372
Control Type (8372) Zone 4
INT
8234
Max power heating % (8234) Zone 4
+ 156.0 HiL_Zone_4
INT
8446
Min power heating % (8446) Zone 4
+ 158.0 ALn_Zone_4
INT
8218
Max Setpoint (8218) Zone 4
INT
8387
Alarms enabling (8387) Zone 4
+ 162.0 A2r_Zone_4
INT
8407
Alarm 1 reference (8407) Zone 4
INT
8408
Alarm 2 reference (8408) Zone 4
+ 166.0 A2t_Zone_4
INT
8598
Alarm 1 type (8598) Zone 4
INT
8599
Alarm 2 type (8599) Zone 4
+ 170.0 Hbt_Zone_4
INT
8249
Alarm HB type (8249) Zone 4
INT
8248
Delay time for alarm HB (8248) Zone 4
+ 84.0 Cit_Zone_2
+ 90.0 AL1_Zone_2
+ 96.0 tYP_Zone_3
+ 100.0 HStA_Zone_3
+ 104.0 HpH_Zone_3
+ 110.0 ALn_Zone_3
+ 116.0 A1t_Zone_3
+ 122.0 Hbt_Zone_3
+ 128.0 CPb_Zone_3
+ 132.0 Cit_Zone_3
+ 136.0 Cdt_Zone_3
+ 142.0 ALHb_Zone_3
+ 148.0 HStA_Zone_4
+ 154.0 HpL_Zone_4
+ 160.0 A1r_Zone_4
+ 164.0 A1t_Zone_4
+ 168.0 HbF_Zone_4
34
Type
2055
Heating Integral Time (2055) Zone 2
80419B_MSW_PROFINET per GFXtermo4-GFX4_06-2014_FRA
Address
Name
+ 172.0 Lbt_Zone_4
Type
INT
Initial
value
Comment
8236
Delay time for alarm LBA (8236) Zone 4
8197
Heating Proportional bande (8197) Zone 4
+ 174.0 HPb_Zone_4
INT
+ 178.0 Hit_Zone_4
INT
8198
Cooling Proportional bande (8198) Zone 4
INT
8199
Heating Integral Time (8199) Zone 4
INT
8268
Cooling Integral Time (8268) Zone 4
+ 176.0 CPb_Zone_4
+ 180.0 Cit_Zone_4
+ 182.0 Hdt_Zone_4
INT
8200
Heating Derivative Time (8200) Zone 4
+ 186.0 AL1_Zone_4
INT
8269
Cooling Derivative Time (8269) Zone 4
INT
8204
Alarm 1 Min Temp (8204) Zone 4
+ 190.0 ALHb_Zone_4
INT
8205
Alarm 2 Max Temp (8205) Zone 4
INT
8247
Alarm Hb Amper (8247) Zone 4
+ 184.0 Cdt_Zone_4
+ 188.0 AL2_Zone_4
= 192.0
END_STRUCT
80419B_MSW_PROFINET per GFXtermo4-GFX4_06-2014_FRA
35
DB20
Liste des paramètres utilisés dans FB15
Address
Name
0.0
+ 0.0 tYP_Zone_1
+ 2.0 HiS_Zone_1
+ 4.0 HStA_Zone_1
+ 6.0 Ctr_Zone_1
+ 8.0 HpH_Zone_1
+ 10.0 HpL_Zone_1
+ 12.0 HiL_Zone_1
STRUCT
Initial
value
Comment
INT
2
INT
1000
Probe/Input type Zone 1
Max Input Zone 1
INT
1400
Max limit TA Zone 1
INT
14
INT
1000
Control Type Zone 1
Max power heating % Zone 1
INT
0
Min power heating % Zone 1
INT
300
Max Setpoint Zone 1
INT
19
Alarms enabling Zone 1
+ 18.0 A2r_Zone_1
INT
0
Alarm 1 reference Zone 1
INT
0
Alarm 2 reference Zone 1
+ 22.0 A2t_Zone_1
INT
3
Alarm 1 type Zone 1
+ 24.0 HbF_Zone_1
INT
2
Alarm 2 type Zone 1
INT
0
Alarm HB type Zone 1
+ 28.0 Lbt_Zone_1
INT
30
Delay time for alarm HB Zone 1
INT
300
Delay time for alarm LBA Zone 1
INT
12
Heating Proportional bande Zone 1
INT
10
Cooling Proportional bande Zone 1
+ 36.0 Cit_Zone_1
INT
527
Heating Integral Time Zone 1
INT
100
Cooling Integral Time Zone 1
+ 40.0 Cdt_Zone_1
INT
131
Heating Derivative Time Zone 1
INT
100
Cooling Derivative Time Zone 1
INT
-10
Alarm 1 Min Temp Zone 1
INT
20
Alarm 2 Max Temp Zone 1
INT
360
Alarm Hb Amper Zone 1
INT
2
INT
1000
Max Input Zone 2
INT
1400
Max limit TA Zone 2
INT
14
INT
1000
+ 14.0 ALn_Zone_1
+ 16.0 A1r_Zone_1
+ 20.0 A1t_Zone_1
+ 26.0 Hbt_Zone_1
+ 30.0 HPb_Zone_1
+ 32.0 CPb_Zone_1
+ 34.0 Hit_Zone_1
+ 38.0 Hdt_Zone_1
+ 42.0 AL1_Zone_1
+ 44.0 AL2_Zone_1
+ 46.0 ALHb_Zone_1
+ 48.0 tYP_Zone_2
+ 50.0 HiS_Zone_2
+ 52.0 HStA_Zone_2
+ 54.0 Ctr_Zone_2
+ 56.0 HpH_Zone_2
+ 58.0 HpL_Zone_2
Probe/Input type Zone 2
Control Type Zone 2
Max power heating % Zone 2
INT
0
+ 62.0 ALn_Zone_2
INT
300
Max Setpoint Zone 2
INT
19
Alarms enabling Zone 2
+ 66.0 A2r_Zone_2
INT
0
Alarm 1 reference Zone 2
+ 68.0 A1t_Zone_2
INT
0
Alarm 2 reference Zone 2
INT
3
Alarm 1 type Zone 2
+ 72.0 HbF_Zone_2
INT
2
Alarm 2 type Zone 2
INT
0
Alarm HB type Zone 2
INT
30
Delay time for alarm HB Zone 2
INT
300
Delay time for alarm LBA Zone 2
INT
12
Heating Proportional bande Zone 2
INT
10
Cooling Proportional bande Zone 2
+ 60.0 HiL_Zone_2
+ 64.0 A1r_Zone_2
+ 70.0 A2t_Zone_2
+ 74.0 Hbt_Zone_2
+ 76.0 Lbt_Zone_2
+ 78.0 HPb_Zone_2
+ 80.0 CPb_Zone_2
36
Type
Min power heating % Zone 2
80419B_MSW_PROFINET per GFXtermo4-GFX4_06-2014_FRA
Address
Name
+ 82.0 Hit_Zone_2
Type
INT
Initial
value
Comment
527
Heating Integral Time Zone 2
100
Cooling Integral Time Zone 2
+ 84.0 Cit_Zone_2
INT
+ 88.0 Cdt_Zone_2
INT
131
Heating Derivative Time Zone 2
+ 90.0 AL1_Zone_2
INT
100
Cooling Derivative Time Zone 2
INT
-10
Alarm 1 Min Temp Zone 2
+ 94.0 ALHb_Zone_2
INT
20
Alarm 2 Max Temp Zone 2
+ 96.0 tYP_Zone_3
INT
360
Alarm Hb Amper Zone 2
INT
2
+ 100.0 HStA_Zone_3
INT
1000
Max Input Zone 3
+ 102.0 Ctr_Zone_3
INT
1400
Max limit TA Zone 3
INT
14
+ 106.0 HpL_Zone_3
INT
1000
Max power heating % Zone 3
INT
0
Min power heating % Zone 3
INT
300
Max Setpoint Zone 3
INT
19
Alarms enabling Zone 3
INT
0
Alarm 1 reference Zone 3
INT
0
Alarm 2 reference Zone 3
INT
3
Alarm 1 type Zone 3
INT
2
Alarm 2 type Zone 3
INT
0
Alarm HB type Zone 3
INT
30
Delay time for alarm HB Zone 3
+ 86.0 Hdt_Zone_2
+ 92.0 AL2_Zone_2
+ 98.0 HiS_Zone_3
+ 104.0 HpH_Zone_3
+ 108.0 HiL_Zone_3
+ 110.0 ALn_Zone_3
+ 112.0 A1r_Zone_3
+ 114.0 A2r_Zone_3
+ 116.0 A1t_Zone_3
+ 118.0 A2t_Zone_3
+ 120.0 HbF_Zone_3
+ 122.0 Hbt_Zone_3
+ 124.0 Lbt_Zone_3
+ 126.0 HPb_Zone_3
+ 128.0 CPb_Zone_3
+ 130.0 Hit_Zone_3
Probe/Input type Zone 3
Control Type Zone 3
INT
300
Delay time for alarm LBA Zone 3
INT
12
Heating Proportional bande Zone 3
INT
10
Cooling Proportional bande Zone 3
INT
527
Heating Integral Time Zone 3
+ 134.0 Hdt_Zone_3
INT
100
Cooling Integral Time Zone 3
INT
131
Heating Derivative Time Zone 3
+ 138.0 AL1_Zone_3
INT
100
Cooling Derivative Time Zone 3
+ 140.0 AL2_Zone_3
INT
-10
Alarm 1 Min Temp Zone 3
INT
20
Alarm 2 Max Temp Zone 3
+ 144.0 tYP_Zone_4
INT
360
INT
2
INT
1000
Max Input Zone 4
INT
1400
Max limit TA Zone 4
+ 132.0 Cit_Zone_3
+ 136.0 Cdt_Zone_3
+ 142.0 ALHb_Zone_3
+ 146.0 HiS_Zone_4
+ 148.0 HStA_Zone_4
+ 150.0 Ctr_Zone_4
Alarm Hb Amper Zone 3
Probe/Input type Zone 4
INT
14
+ 154.0 HpL_Zone_4
INT
1000
Max power heating % Zone 4
INT
0
Min power heating % Zone 4
+ 158.0 ALn_Zone_4
INT
300
Max Setpoint Zone 4
INT
19
Alarms enabling Zone 4
INT
0
Alarm 1 reference Zone 4
INT
0
Alarm 2 reference Zone 4
INT
3
Alarm 1 type Zone 4
INT
2
Alarm 2 type Zone 4
INT
0
Alarm HB type Zone 4
INT
30
Delay time for alarm HB Zone 4
+ 152.0 HpH_Zone_4
+ 156.0 HiL_Zone_4
+ 160.0 A1r_Zone_4
+ 162.0 A2r_Zone_4
+ 164.0 A1t_Zone_4
+ 166.0 A2t_Zone_4
+ 168.0 HbF_Zone_4
+ 170.0 Hbt_Zone_4
80419B_MSW_PROFINET per GFXtermo4-GFX4_06-2014_FRA
Control Type Zone 4
37
Address
Name
+ 172.0 Lbt_Zone_4
+ 174.0 HPb_Zone_4
+ 176.0 CPb_Zone_4
+ 178.0 Hit_Zone_4
+ 180.0 Cit_Zone_4
+ 182.0 Hdt_Zone_4
+ 184.0 Cdt_Zone_4
+ 186.0 AL1_Zone_4
+ 188.0 AL2_Zone_4
+ 190.0 ALHb_Zone_4
= 192.0
Type
INT
Initial
value
Comment
300
Delay time for alarm LBA Zone 4
INT
12
Heating Proportional bande Zone 4
INT
10
Cooling Proportional bande Zone 4
INT
527
Heating Integral Time Zone 4
INT
100
Cooling Integral Time Zone 4
INT
131
Heating Derivative Time Zone 4
INT
100
Cooling Derivative Time Zone 4
INT
-10
Alarm 1 Min Temp Zone 4
INT
20
Alarm 2 Max Temp Zone 4
INT
360
Alarm Hb Amper Zone 4
END_STRUCT
GEFRAN S.p.A.
via Sebina, 74
25050 Provaglio d’Iseo (BS) Italy
Tel. 030 98881 - Fax 030 9839063
www.gefran.com
38
80419B_MSW_PROFINET per GFXtermo4-GFX4_06-2014_FRA